06-23-2009 03:00 AM
I have a CAT 3406 genset with 103-1837-3 control panel. I am trying to connect the remote auto starting signal to this control board and cannot find the correct point for connections. I have no wiring diagram and local CAT dealer is not much help. The serial for the genset is 2WB17170. Can someone please help me on this. Thanks a lot.
Re: CAT 3406 (1995) Genset Remote Start
- Mark as New
- Bookmark
- Subscribe
- Subscribe to RSS Feed
- Highlight
- Email to a Friend
- Report Inappropriate Content
06-24-2009 09:26 AM
Hi
The number you supplied is the sticker on the panel. I am sure you have the EMCP 2 type control panel.
You need to wire across terminal 57 and 30. If in auto and these are connected then the engine will start.
If you have an email address i can send you the drawing.
regards
Mick
Re: CAT 3406 (1995) Genset Remote Start
- Mark as New
- Bookmark
- Subscribe
- Subscribe to RSS Feed
- Highlight
- Email to a Friend
- Report Inappropriate Content
06-25-2009 02:09 AM
Hi: Thanks for the help. The control panel infact is EMCP2, Panel type: 103-1582. I will let you know about the result but really appreciate your help. My email is AMIT@VIDHILTD.com and would be really nice if you could send me the wiring diagram. Thanks again
Re: CAT 3406 (1995) Genset Remote Start
- Mark as New
- Bookmark
- Subscribe
- Subscribe to RSS Feed
- Highlight
- Email to a Friend
- Report Inappropriate Content
06-25-2009 04:11 AM
Hi Mick:
I was looking at the control panel and couldnot find terminal 57. If I have your email, I can send you pics of the inside or can you please send me the wiring diagram. Thanks again for all your help.
Regards,
Amit
Re: CAT 3406 (1995) Genset Remote Start
- Mark as New
- Bookmark
- Subscribe
- Subscribe to RSS Feed
- Highlight
- Email to a Friend
- Report Inappropriate Content
02-18-2010 01:55 AM
Dears Amit/Mick i have problem in my control panel and wiring diagram type 103-1582 i hope yoy help me as soon as possible
regards,
my email: fsalih@gnpoc,com
Re: CAT 3406 (1995) Genset Remote Start
- Mark as New
- Bookmark
- Subscribe
- Subscribe to RSS Feed
- Highlight
- Email to a Friend
- Report Inappropriate Content
03-26-2011 11:26 PM
2 and 14
Re: CAT 3406 (1995) Genset Remote Start
- Mark as New
- Bookmark
- Subscribe
- Subscribe to RSS Feed
- Highlight
- Email to a Friend
- Report Inappropriate Content
03-28-2011 08:43 PM
For EMCPII Control panel, the remote start signal: link wire 57 and 30, 30 is linked to negative(-).
NEED CAT 6V6153 EMCP 2 CONTROLER FOR CAT 3406 (1995) Genset Remote Start
- Mark as New
- Bookmark
- Subscribe
- Subscribe to RSS Feed
- Highlight
- Email to a Friend
- Report Inappropriate Content
06-20-2012 06:01 PM
PLEASE SEND THE ATS CONECTION AND REMOTE START FOR A CAT 3406 GEN SET SERIAL 2WB15824 ARRNG 9Y8245 I NEED A EMCP 2 CONTROLLER FOR THIS UNIT COULD YOU PLEASE SEND PRICE I COULD USE AN USED ONE 6V6153
THANKS
MARCO ANSELMETTI
DIESEL POWER CA
VENEZUELA