Home
Products
Applications
Parts & Service
Rental
News & Events
About The Company
Reply
Cat Dealer
wtc2008

J1939 communication with control panel

For CAT genset with ECM, local control panel communicate with engine ECM and get information through J1939

Now, I want to remain the local control panel and increase one  Remote Control Panel.

 I hope the remote control panel also get infrmation from ECM through J1939.

Are there any problems? Does any experience this?

 

Regards,

 

wtc2008

Visitor
esantos

Re: J1939 communication with control panel

Hi wtc2008

I have a lot of projects with CAT gensets equipped with EMCP3 and ECM. They work in parallel wiht other gensets and/or with the grid. For that, it was necessary to install another module to sync and share load. We connect J1939 of the EMCP together with this new module and we don't have any problem. The new module can read many data from J1939 and the baud rate remains the same. Make sure to use the right cable and put 120 ohm resistor at the end of the line. 

Regards
E. Santos
Cat Dealer
wtc2008

Re: J1939 communication with control panel

Thanks. E. Santos
Visitor
Engine-tech

Re: J1939 communication with control panel

I advice you to use Murphy  PV101 using J1939  its monitor all parameters also active and logged codes .

 

http://www.fwmurphy.co.uk/products/murphylink_j1939/j1939_powerview_pv101.htm